Control Valves ~ Learning Instrumentation And Control Engineering Learning Instrumentation And Control Engineering

Control Valve Actuators Failure Modes

Custom Search

Control valves can be built from various combinations of valve actuator and valve body. The combination of actuator and valve body is usually chosen to provide a particular failure mode should the instrument air supply fail for any reason.
The most common control valve actuator used in the industry is the diaphragm actuator. Diaphragm actuators, as in the case of valve bodies, can be classified as either direct or reverse acting. 


Any failure mode can be obtained with a combination of direct or reverse acting
actuator and direct or reverse acting valve body. The two most common failure mode of control valves are :

1. Fail Open
2. Fail Close

These two failure modes can be achieved by an Air to Close Valve (ATC) and an Air to Open valve (ATO).

Air to Close Control Valve (ATC)
An air to close (ATC) valve and therefore fail open valve, can be obtained with the combination of a reverse acting actuator and a reverse acting valve body or a direct acting actuator and a direct acting valve body.

Air to Open Control Valve (ATO)
An air to open (ATO) valve and therefore fail close valve, can be obtained with a combination of direct actuator and reverse body or reverse actuator and direct Body.

Valve Body and Actuator Combination and Their Failure Modes
The action of an actuator can easily be determined (usually by whether the air is supplied to the upper or lower half of the housing). Direct or reverse acting valve bodies are not always readily identifiable. Most often, reference to the nameplate or flow sheet is usually necessary to correctly identify the action of a valve body – reverse acting or direct acting.

Listed in the table below are all possible combinations of valve body and actuator and their failure modes:

Valve Actuator 
Valve Body
Valve Action
Failure Mode
Direct 
Direct
Air to Close
Fail Open
Reverse
Reverse
Air to Close
Fail Open
Direct
Reverse
Air to Open
Fail Closed
Reverse
Direct
Air to Open
Fail Closed




Basics of Split-Range Control in Control Valve Applications

Custom Search

In many process control applications in industry, it is sometimes desirable to have multiple control valves respond to the output of a single common controller. Control valves configured in this way to follow the command of a single controller are said to be split-ranged, or sequenced.

Split-ranged control valves may assume different forms of sequencing. Common modes of control valve sequencing seen in the process industry are:  complementary, exclusive, and progressive.

Complementary Split-Range Control
With this form of split-ranging, there is never a condition in the controller’s output range where both valves are fully open or fully shut. Rather, each valve complements the other’s position.  A typical example of complementary split-range control is a situation where two valves serve to proportion a mixture of two fluid streams, such as where base and pigment liquids are mixed together to form colored paint as shown below:
Example of complementary split-range control.


Both base and pigment valves operate from the same controller output signal. While the pigment valve is Air-To-Open, the base valve is Air-To-Close. The following table shows the relationship between valve opening for each control valve and the controller’s output:
Controller Output (%)
I/P Output (PSI)
Pigment Valve (Stem position)
Base Valve (Stem position)
0
3
Fully Closed
Fully Open
25
6
25% Open
75% Open
50
9
Half-Open
Half - Open
75
12
75% Open
25% Open
100
15
Fully Open
Fully Closed

Exclusive Split-Range Control
The nature of valve sequencing in this type of split-range control is to have an “EITHER OR” throttled path for process fluid. That is, either process fluid flows through one valve or through the other, but never through both at the same time.

This type of split-ranged control valves call for a form of valve sequencing where both valves are fully closed at a 50% controller output signal, with one valve opening fully as the controller output drives toward 100% and the other valve opening fully as the controller output goes to 0%.

A practical example of this form of split-ranging is in reagent feed to a pH neutralization process, where the pH value of process liquid is brought closer to neutral by the addition of either acid or caustic:
Exclusive Split-Range Control

The basic operating principle of the above process is:
  1. A pH analyzer monitors the pH value of the mixture and a single pH controller commands two           reagent valves to open when needed.

  2. If the process pH begins to increase, the controller output signal increases as well (direct action)         to open up the acid valve.

  3. The addition of acid to the mixture will have the effect of lowering the mixture’s pH value.

  4. Conversely, if the process pH begins to decrease, the controller output signal will decrease as      well, closing the acid valve and opening the caustic valve.

  5. The addition of caustic to the mixture will have the effect of raising the mixture’s pH value.
The Air-To-Open acid valve has an operating range of 9 to 15 PSI, while the Air-To-Close caustic valve has an operating of 9 to 3 PSI. The table below shows the relationship between valve opening for each control valve and the controller’s output:

Controller Output (%)
I/P Output (PSI)
Acid Valve (Stem position)
Caustic Valve (Stem position)
0
3
Fully Closed
Fully Open
25
6
Fully Closed
Half - Open
50
9
Fully Closed
Fully Closed
75
12
Half - Open
Fully Closed
100
15
Fully Open
Fully Closed

Progressive Split-Range Control
This form of split-range control for control valves is used to expand the operating range of flow control for some fluid beyond that which a single control valve could deliver. In this type of control, one of the valve usually a small valve opens gradually and becomes fully open at 50% of controller output while the large valve will remain shut at until the controller output goes beyond 50% when it starts opening. Both valves become fully open when controller output is 100%.

An example of progressive split-range control is a pH control process where the incoming liquid always has a high pH value, and must be neutralized with acid as shown below:
An example of progressive split-range control

The PH of the incoming water to be treated is measured by the analyzer, AT. As the output of controller AIC increases, the small acid valve starts to open and becomes fully open at 50% of controller output. Meanwhile the large acid valve will remain shut until controller output goes beyond 50%. At 100%, both small and large acid valves are fully open to ensure that the PH of the incoming water is neutralized.

Controller output and valve status for proper sequencing of the small and large acid control valves is shown below:

Controller Output (%)
I/P Output (PSI)
Small Acid Valve (Stem position)
Large Acid Valve (Stem position)
0
3
Fully Closed
Fully Closed
25
6
Half Open
Fully Closed
50
9
Fully Open
Fully Closed
75
12
Fully Open
Half Open
100
15
Fully Open
Fully Open




ANSI B16.5 - Maximum Pressure and Temperature Ratings of Flanges and Flange Fittings

Custom Search

The Maximum allowable non-shock pressure (psig) and temperature ratings for steel pipe flanges and flanged fittings according the American National Standard ANSI B16.5 are given in the table below. 

Flanges and their Fittings are a common feature in the process plants. The need to accurately determine their pressure rating and corresponding temperature ratings is important for personnel and plant safety and overall plant performance and reliability:


Maximum Allowable Non-Shock Pressure (Psig)
Temperature (°F)
Pressure Class (lb)
150
300
400
600
900
1500
2500
Hydrostatic Test Pressure (Psig)
450
1125
1500
2225
3350
5575
9275
-20 to 100
285
740
990
1480
2220
3705
6170
200
260
675
900
1350
2025
3375
5625
300
230
655
875
1315
1970
3280
5470
400
200
635
845
1270
1900
3170
5280
500
170
600
800
1200
1795
2995
4990
600
140
550
730
1095
1640
2735
4560
650
125
535
715
1075
1610
2685
4475
700
110
535
710
1065
1600
2665
4440
750
95
505
670
1010
1510
2520
4200
800
80
410
550
825
1235
2060
3430
850
65
270
355
535
805
1340
2230
900
50
170
230
345
515
860
1430
950
35
105
140
205
310
515
860
1000
20
50
70
105
155
260
430




Control Valve Selection Requirements

Custom Search

Control valves abound in every area of industrial process control. Control valves handle all kinds of fluids at temperatures from the cryogenic range to well over 1000°F (538°C). Selection of a control valve body assembly requires particular consideration to provide the best available combination of valve body style, material, and trim construction design for the intended service. Capacity requirements and system operating pressure ranges also must be considered in selecting a control valve to ensure satisfactory operation without undue initial expense.

Information required to select a control valve. Photo Credit : Fisher

The numbers in the orange colored circles in the above control valve diagram corresponds to the serial numbers in the table below where we have given the typical information required to select the right control valve. For example serial numbers 1, 2, 3, 4, 5 represents fluid properties corresponding to serial numbers 1, 2, 3, 4,5 in the table below.

To have a clear understanding of the information required to select a control valve which we have discussed in this article, please read the following:
Because of the tendency to get the selection of control valves wrong, most control valve manufacturers and their representatives have dedicated themselves to helping their clients select the control valve most appropriate for the existing service conditions. To aid in selecting the right control valve, the following information must be provided before the actual sizing and selection process:


S/N   
CONTROL VALVE SELECTION INFORMATION
1 Type of fluid to be controlled What fluid will you be controlling? Water?, natural gas? 
2 Temperature of fluid State the worst scenario temperature of the fluid in degree Fahrenheit or Celsius
3 Viscosity of fluid
4 Specific gravity of fluid
5 Flow capacity of the control valve State the maximum and minimum flow rates.
6 Inlet pressure at valve State maximum and minimum inlet pressures expected to be handled by the control valve
7 Outlet pressure at valve State maximum and minimum outlet pressures expected to be handled by the control valve
8 Pressure drop during normal flowing conditions
9 Pressure drop at shut off
10 Noise level State the maximum permissible noise level if required and the measurement reference point e.g 55 dBA
11 Degrees of superheat or existence of flashing if known
12 Inlet and outlet pipeline size and schedule
13 State whether any special tagging information is required for the control valve
14 Body material of the control valve State the required body material of the control valve - ASTM A216 grade WCC, ASTM A217 grade WC9, ASTM A351 CF8M, etc.)
15 End connections and valve ratings Is it going to be screwed? Class 600 RF flanged? Class 1500 RTJ flanges? etc
16 Valve action desired when instrument air fails Is the valve to fail open, close or retains its last controlled position?
17 Instrument Air Availability State whether the valve require instrument air
18 Valve type number Only when required by manufacturer
19 Valve size
20 Valve body construction Is the valve body going to be angle? double-port? Butterfly? etc.
21 Valve port size State whether the valve port size is going to be full or restricted
22 State the desired valve trim materials required
23 Flow action State whether flow will tend to open valve or close valve
24 Actuator size State the size of actuator required for the control valve.
25 Bonnet Style Is the bonnet style going to be plain, extension,
bellows seal, etc.

26 Valve packing materials State the type of valve packing material - PTFE V-ring, laminated graphite, environmental
sealing systems, etc.

27 Valve accessories State the control valve accessories required – positioner, handwheel etc





How to Calibrate a Fisher 3582 Pneumatic Valve Positioner

Custom Search


The valve positioner is a critical component in the control valve loop as it helps to accurately position the valve during the control process. However, failure to calibrate the positioner accurately could lead to wrong valve positioning which could in turn have significant impact on the process where the control valve is being used. Imagine supplying a customer natural gas at 5barg through a control valve controlled by a controller taking signal from the supply to the customer. If pressure suddenly goes to 7barg and the controller gives a signal to the control valve to close more to bring the pressure to 5barg, if the control valve is wrongly positioned and fails to close more, we could be giving the customer more than 5barg! This could be catastrophic and lead to undesirable consequences.

In view of the importance of a positioner in accurately positioning the control valve plug, the need to accurately calibrate the valve positioner cannot be over emphasized. The set up below illustrates the basic components required to calibrate a control valve positioner:


Before studying this procedure, read : How a Pneumatic Valve Positioner Works 

Procedure for Calibrating a Pneumatic Valve Positioner

Step 1
Shut off the supply pressure to the valve positioner. Connect or reconnect the necessary tubing from the valve positioner output to the actuator supply connection. Connect the input to the valve positioner and set the input signal value at mid-range.

Step 2
Move the flapper assembly to approximately position 6 in the proper operating quadrant of the beam (direct or reverse acting), and apply supply pressure to the valve positioner. The 0 degree index marks on the rotary shaft arm should align with the case index marks as shown in diagram below and the actuator should be at its mid-travel position. If not, first check for loose linkage or improper cam installation. A minor nozzle height adjustment might be necessary to make the desired input signal value correspond to the starting point of travel.
Positioner Beam and Arm Index Marks. Photo Credit: Fisher

Step 3
Apply an input signal equal to the low value of the input signal range. If your positioner is a 0.2bar – 1.2 bar range (3 to 15psig) input range, set the input to 3psig. Loosen the nozzle locknut and adjust the nozzle until the actuator moves to the proper end of its travel. Changing the nozzle position is intended only as a means of zero trim adjustment. Whenever nozzle position is changed, the zero reference point is changed. 

Step 4
Apply an input signal equal to the high value of the input signal range (15psig, if using a 3 to 15psig positioner) and observe the actuator stem travel. If the stem travel is short of its expected range, increase the travel by moving the flapper assembly to a higher number on the beam. If the desired stem travel occurs before the input signal reaches the high value of the input signal range, decrease the travel by moving the flapper assembly toward a lower number on the beam.

Step 5
Repeat steps 3 and 4 until the correct travel is achieved. Each time the flapper assembly position is changed in step 4, repeat step 3 to provide proper zero. Note that Moving the flapper assembly toward zero on the beam scale decreases stem travel.





Process Performance of Correctly Sized, Undersized and Oversized Control Valves

Custom Search

In the process of sizing and selecting control valves, there is one of three possible outcomes:
1. The valve is correctly sized or 
2. The valve is oversized or
3. The valve is undersized

Characteristics of Correctly Sized, Under-sized and Over-sized Control Valves

A Correctly Sized Control Valve (The right valve Cv)
A correctly sized valve has the required capacity to deliver the right flow rate at minimum, normal and maximum flows and helps to safeguard optimal control both as far as comfort and economy are concerned.

Oversized Control Valves (Large Cv)
An oversized valve has poor controllability. An oversized control valve implies that all normal operations will be confined to small openings of the valve with great risk of variable sensitivity and aggravation of any uneven movement of the valve. Poor accuracy and unstable control often result.
The smallest change in stroke in an oversized valve will result in large flow variations. As the valve opens or closes, large flow speeds and a powerful turbulence are created between the plug and seat. This both erodes the valve and causes noise. 

Undersized Control Valves (Small Cv)
If the control valve is undersized (Cv - too small), the required flow rate will not be achieved even when the valve is fully opened. If a higher pressure is applied to force a higher flow rate across the undersized valve; not only the pump energy will be excessive but also the valve may cavitate or develop flashing.





Pressure Drop Regimes Across a Control Valve

Custom Search

Control valves are critical elements in industrial process control. They are used for controlling various types of fluid. However as fluid passes across a control valve, the pressure regimes across the valve especially pressure drop changes with flow. A basic understanding of the pressure regimes across a control valve will help in the valve sizing process.

To accurately size a control valve, we must correctly predict the pressure drop across the valve from minimum flow to normal to maximum flow.

Typically as flow increases across a valve, the pressure drop across the valve reduces until it gets to the minimum allowable pressure drop across the valve at maximum fluid flow. As flow decreases, the pressure drop across the valve increases commensurately. These variations are illustrated in the diagram below:


As shown in the diagram above:
1. As flow increases across the valve , upstream pressure P1 drops
2. The pressure drop across the valve, ∆P, decreases as flow increases
3. At zero flow, ∆P is maximum and the downstream pressure P2 = 0
4. As flow increases, downstream pressure, P2 increases.
5. At maximum flow across the valve, ∆P is minimum





How a Pneumatic Valve Positioner Works

Custom Search

The pneumatic valve positioner accepts an input pneumatic signal from a control device and sends an increased or decreased output signal to a control valve to ensure the control valve plug travels correctly and is positioned properly on the valve seat. The schematic below illustrates how the valve positioner is connected to the control valve:

A valve positioner can be set to either direct-acting or reverse-acting. A direct-acting valve positioner sends an increased output signal to the control valve as the input signal to it increases. A reverse-acting valve positioner, sends a decreased output signal as the input signal to it increases.

How the Pneumatic Valve Positioner Works
The schematic below is that of a direct-acting Fisher 3582G pneumatic valve positioner:
Fisher 3582G Pneumatic Valve Positioner (Photo Credit : Fisher)

As shown in the diagram, the valve positioner is attached to a diaphragm-actuated sliding stem control valve. The supply pressure is connected to a pneumatic relay. A fixed orifice restriction in the relay limits flow to the nozzle such that when the flapper is not restricting the nozzle, air can bleed out faster than is being supplied.

The input signal from the control device is connected to the bellows. When the input signal increases, the bellows expand and moves the beam. The beam pivots about the input axis moving the flapper closer to the nozzle. The nozzle pressure increases and through the pneumatic relay action increases the output pressure to the valve actuator. The increased output pressure to the actuator causes the actuator stem to move downward. Stem movement is then fed back to the beam by means of a cam. As the cam rotates, the beam pivots about the feedback axis to move the flapper slightly away from the nozzle. The nozzle pressure decreases and reduces the output pressure to the actuator. Stem movement continues backing the flapper away from the nozzle until equilibrium is achieved.

When the input pressure decreases, the bellows contracts (aided by an internal range spring) and the beam pivots about the input axis to move the flapper away from the nozzle. Nozzle pressure decreases and the pneumatic relay permits the release of diaphragm casing pressure to atmosphere causing the actuator stem to move upward. Through the cam, stem movement is fed back to the beam to re-position the flapper closer to the nozzle. When equilibrium conditions are attained, stem movement stops and the flapper is positioned to prevent any further decrease in diaphragm case pressure.

In a reverse-acting valve positioner, the same basic operating principle above applies except that as the input signal increases, the diaphragm casing pressure is decreased. A decreasing input signal causes an increase in pressure to the diaphragm casing of the control valve.

How to Change Valve Positioner Action of the 3582G Pneumatic Valve Positioner
Positioner Beam (Photo Credit: Fisher)

The position of the flapper assembly on the beam determines whether the valve positioner will act as direct-acting or reverse-acting.  

As shown in the diagram above, the  beam is divided into quadrants. The direct acting quadrant is labelled DIRECT and the reverse-acting quadrant is labelled REVERSE. To change the valve positioner action, simply move the flapper assembly to the opposite quadrant of the beam.




How to Use a Solenoid Operated Valve to Implement Emergency Shutdown.

Custom Search

One of the commonest configurations of Solenoid operated valves in use in valve emergency shutdown system is the 3-way valve. These three-way solenoid valves are typically installed in instrument air signal lines, between an instrument air supply to a control valve that is part of an emergency shutdown system.

When used in these emergency shutdown systems, the solenoid valve is energized during normal operation with an electric current and allows the instrument air signal to pass through to the control valve actuator. When the solenoid is de-energised by a remote hand switch, electrical failure or by an automatic emergency trip, the air signal is vented to atmosphere from the control valve and the air supply is isolated. The control valve then moves to its fail safe position on loss of air pressure.

An example of the use of a solenoid valve for emergency signal air switching, in a furnace firing control loop is illustrated below:

During normal operation, the temperature of the heated oil stream is controlled by temperature controller, TC-1, which controls the pressure of fuel gas to the burners indirectly by cascade control of the fuel gas pressure controller PC-2.

If the hot oil temperature exceeds its safe upper limit denoted by, HH (High High) then the high temperature trip instrument TZA-3 de-energizes the solenoid valve in the signal line between PC and its control valve. The control valve then closes to its minimum stop. When temperature falls below the HH limit, the solenoid valve is re-energized permitting fuel gas into the burners for more heating.




How a Solenoid Valve Works

Custom Search



As shown above, a solenoid valve is made up of two basic functional units. They are
(1) The solenoid, an electro-magnet with a plunger.
(2) A valve containing an orifice in which a disc or plug is positioned to stop or allow flow.
The valve is opened or closed by movement of the magnetic plunger, or core, which is drawn into the solenoid when the coil is energised (an electric current is passed through it). In A above, the solenoid valve opens when energized allowing instrument air to pass through. In B, the valve closes when the solenoid is de-energized preventing instrument air from passing through but vented to the atmosphere
Solenoid valves have a solenoid mounted directly on the valve body with the solenoid core attached to the valve stem. The core is enclosed and free to move in a permanently sealed tube inside the solenoid coil. This construction provides a compact, leak tight assembly.

Solenoid Valve Configurations And Ratings
Solenoids are often used in valve pneumatic controls to activate the valve. In their simplest form, there are 2-way, 3-way and 4-way pneumatic valves. A 2-way pneumatic valve typically has two outlet ports for instrument air flow in and out. A 3-way valve has two outlet ports and one exhaust or vent port. A 4-way valve has two outlet ports and two exhaust ports and it switches air supply between the two outlet ports. 2-way can be normally open (NO) or normally closed (NC), terms that refer to their normal states without power applied.

Solenoid operated valves use an electrical coil to control the position of a poppet, plunger or spool to open or close a valve. Typical solenoid control voltages are 12VDC, 24 VAC/DC, 120VAC or 240VAC.
 




How to Adjust the Bench Set of a Control Valve Actuator

Custom Search

As already explained in Control Valve Actuator Bench Set and Valve Stroking, the bench set of a control valve is the pressure range required to stroke the valve from a fully closed to a fully open position.
The bench set pressure range is used to adjust the initial compression of an actuator spring with the valve assembly “on the bench” The correct initial compression is important for the proper operation of the valve-actuator assembly when it is put into service and the proper actuator diaphragm operating pressure is applied.

The bench set range is established with the assumption that there is no packing friction. Accurate adjustment to the bench set range can easily be made during actuator mounting process by making the adjustment before the actuator is connected to the valve assembly.

When attempting to adjust the spring in the field, it is very difficult




Rules of Thumbs for Sizing Control Valves

Custom Search

In many applications where control valves are applied, sizing and selection can be quite challenging. In the majority of applications, it is either the control valve is under sized or over-sized. In an undersized control valve, the valve is unable to deliver the required flow for each stage of the valve lift creating control problems.

Over-sized control valves will under all normal operations be confined to small openings of the valve with great risk of variable sensitivity and aggravation of any uneven movement of the valve and actuator combination. Poor accuracy and unstable control are often the result of over-sized control valves.

Given the problems that could arise because of failure to size control valves accurately, the following rules of thumb are presented as a guide for the selection and sizing of control valves:




How a Temperature Control Valve Works

Custom Search

A temperature control valve is just like any other control valve. The only difference is that the control valve helps to maintain the temperature of a desired process at a specific level. It is often abbreviated as TCV – Temperature Control Valve – in most process drawings and P&IDs.

Temperature Control Schemes
There are two popular temperature control schemes using temperature control valves:
(1) Mixing of a cold process fluid with a hot process fluid to control the temperature of the hot process fluid.
(2) Exchange of heat between the hot process fluid and a cold process fluid as seen in heat exchangers. However, the process fluids do not mix.

Mixing of Cold and Hot Process Fluids
In temperature control valve applications in its most basic form, there are two basic process fluids:




How to Measure Control Valve Deadband

Custom Search

What is Deadband ?
Dead band can be caused by packing friction, unbalanced forces and other factors in the control valve assembly. In technical terms, control valve deadband is the range a measured signal can vary without initiating a response from the actuator. The schematics below illustrates the concept of deadband for direct and reverse acting control valve actuators:

Every control valve actuator has




Basics of Control Valve Sizing – Key Terms & concepts

Custom Search

Pressure Drop
The difference in pressure between upstream and downstream the control valve, caused by resistance to flow. Pressure drop is pressure loss across the valve created by system demand - NOT by the valve alone.

How to Determine Pressure Drop
To determine ΔP across a valve, subtract the outlet pressure (P2) from the inlet pressure (P1).
ΔP = P2 – P1

Importance of Pressure Drop in Valve Sizing
Pressure drop is a critical element in valve sizing and valve application. Pressure drop must be known by the engineer designing the system to ensure proper valve selection

What Determines Valve Pressure Drop?

The critical factors are orifice size and internal flow paths of the valve.


Relationship between the Flow Rate and Pressure Drop across a Control Valve
Pressure drop and flow rate are dependent on one another. The higher the flow rate through a restriction(control valve), the greater the pressure drop. Conversely, the lower the flow rate, the




How to Size a Control Valve for Liquid and Gas Applications Using a Selection Chart

Custom Search

Control valve sizing is big business. Often there is a thin line between getting it right or wrong with unintended consequences for the process where the control valve is applied. Typically these days, most control valve sizing is done via software supplied by valve manufacturers. However, here the sizing chart presented is a guide for quickly selecting the type of valve required for general-purpose applications before getting down to the nitty-gritty of using a sizing software.  As you examine this selection chart, please be reminded that there are so many special circumstances applicable to many control valve applications that the guide provided here be considered as a very approximate first level guide only.
Before using this chart, make sure you understand the terms, P1, P2 and T1 as defined in the schematic for a control valve in a process shown below:




How to Specify Control Valves

Custom Search

Control valves handle all kinds o fluids at temperatures ranging from the cryogenic range to well over 10000 degree Fahrenheit (538 degree Celsius). Selection of a control valve assembly requires particular consideration to provide the best available combination of valve body style, material, and trim construction design for the intended service. Capacity requirements and system operating pressure ranges must also be considered in selecting the right control valve to ensure satisfactory operation without undue initial expense.

Most times the control valve manufacturers and their representatives will help in selecting the most appropriate control valve for a given service conditions. However they require the right set of information to be able to do this as there are several possible correct choices for any given application.

To select a given control valve for any application, follow the steps in the chart below




Control Valve Body Materials

Custom Search


The medium or substance flowing through a valve will often determine the type of valve body material. Some valve body materials are best suited for high temperature applications while others are best suited for their corrosion resistance to fluid substance still others are selected based on a low cost factor. Most times, manufacturers of valves will aid you in selecting the right valve for a given application after supplying the needed information.




Smart Valve Positioners

Custom Search

Smart valve positioners are digital valve controllers, microprocessor-based, current to pneumatic instruments with internal logic capability. They are designed to convert a current signal to a pressure signal to operate a valve. The ability to embed software commands into the memory of these smart digital controllers represents the real difference between digital and analog I/P devices. The software capability allows automatic configuration and setup of the valve when equipped with a digital controller. Most importantly, it allows two-way communication for process, valve, and instrument diagnostics.

Reasons for the Use of Smart Positioners
In most respects smart positioners perform the same basic function as the basic analogue positioners combined with current to pneumatic converters. However, the key advantages for using smart positioners are:
  • Automatic calibration and configuration. Considerable time savings are realized over traditional zero and spanning.
  • Valve diagnostics. Through the Distributed Control System (DCS), PC software tools, or handheld communicators, users can diagnose the health of a control valve while it is in the line.
  • Reduced cost of loop commissioning, including installation and calibration.
  • Use of diagnostics to maintain loop performance levels
  • Improved process control accuracy that reduces process variability




The Valve Flow Coefficient (Cv)

Custom Search

The valve flow coefficient Cv or its metric equivalent Kv has been adopted universally as a comparative value for measuring the capacity of control valves. 
The valve flow coefficient, Cv, is the number of U.S. gallons per minute of water at 60°F that will flow through a control valve at a specified opening when a pressure differential of 1psi is applied across the valve:
The metric equivalent of Cv is Kv, which is defined as the amount of water that will flow in m3/hr with 1bar pressure drop. Converting between