How to Reduce Electromagnetic Interference (EMI) in Control Loops and Instrumentation Systems.

Custom Search

What is Electromagnetic Interference (EMI)?
Electromagnetic Interference (EMI) means the presence of undesirable interference voltages in a control loop or instrumentation system.  These undesirable voltages are generated by time changing external electric or magnetic fields emanating from such sources as:
  • Electric motors
  • Transformers
  • Power lines
  • Thyristors used in certain electronic devices
  • High frequency radiation
  • Leakage currents due to damaged electrical heaters
Electromagnetic Compatibility (EMC) of Instruments
The ability of an instrument or instrumentation system to withstand or suppress interference is defined as Electromagnetic Compatibility (EMC)

How to Reduce EMI in Measurement and Instrumentation systems
There are a variety of methods that have proven to be successful in combating electromagnetic interference in measurement and instrumentation systems. Some of these methods are briefly discussed below.

EMI Due to Electrical Alternating Current (AC) Fields
The interference due to electrical AC fields can be reduced by adequately shielding the connection wires.
Magnetic Induced EMI
The effect of magnetic induced interference is difficult to reduce using conventional shielding methods. One practical solution that has worked very well is to space the measurement circuit from the EMI sources as far apart as possible. Where interference is still possible after spacing as far as possible, the measurement connection leads should be very close to each other and in parallel if possible.

Twisted pairs or coaxial cables provide good protection against alternating current (AC) magnetic fields interference in instrumentation circuits by shortening the interference sensitive signal path and transmitting the signal over the remaining path by using the milliamps (mA) output signals from a very good transmitter.

EMI Due to Ground Loops
Ground loops are introduced in measurement system due to poor earthing practice. They are caused by currents flowing as a result of the differing ground potentials in a measurement circuit. Ground loops can effectively be suppressed by using grounded metallic sheath for the instrumentation measurement circuit.




How a 2 Wire Transmitter 4 – 20mA Current Loop Works

Custom Search

In two-wire 4-20mA control loops which are the most popular these days, the 2-wire transmitters convert various process signals representing flow, level, temperature, pressure, etc., to 4-20mA DC current for the purpose of transmitting the signal over some distance with little or no loss of signal.

Relationship between the Components in the 4 – 20mA Control Loop
There are three key components in the 4 – 20mA loop as shown below:

They are:




Basics of The 4 - 20mA Current Loop

Custom Search

The 4-20mA current loop is a very robust and popular sensor signalling standard. Current loops are ideal for data transmission because of their inherent insensitivity to electrical noise. In a 4-20mA current loop, all the signalling current flows through all devices. All the devices in the loop drop voltage due to the signal current flowing through them. The signalling current is not affected by these voltage drops as long as the power supply voltage is greater than the sum of the voltage drops around the loop at the maximum signal current of 20mA.


As shown in the diagram above, current supplied from the power supply flows through the loop wires with resistance, RW, to the transmitter and the 4 – 20mA transmitter regulates the current flow within the loop. The current allowed by the transmitter is called the loop current and it is proportional to the parameter that is being measured. The loop current flows back to the controller through the wire, and then flow through resistor, R, to ground and returns to the power supply. The current flowing through R produces a voltage that is easily measured by the analog input of a controller. For a 250 ohm resistor, the voltage will be 1VDC at 4mA and 5VDC at 20mA.




4 - 20mA Transmitter Wiring Types: 2 -Wire, 3 - Wire & 4 - Wire

Custom Search


Today’s electronic process transmitters - pressure, temperature, flow and level are connected in different wire types or configurations. These connection methods are of great concern to the instrument engineer/technician. The 2 - Wire, 3 - Wire and 4 - Wire types are often used to describe the method of connection of electronic transmitters. However in today's rapidly evolving technological world, the 2 - Wire type transmitter is by far the most common. Evidently so because of the huge savings in wiring and other advantages it possess over the other transmitter wire configurations.


Two wire transmitters:

These are the simplest and most economical and should be used wherever load conditions will permit. They are often called loop powered instruments. In a 2 -wire system, the only source of power to the transmitter is from the signal loop. The 4 mA zero-end current is sufficient to drive the internal circuitry of the transmitter and the current from 4 to 20 mA represents the range of the measured process variable. The power supply and the instruments are usually mounted in the control room. The schematic diagram below shows the wire transmitter configuration:




Instrumentation Basics: 4 - 20mA and 3 - 15psi Control Signals

Custom Search

In the field of instrumentation, analogue electronic signals and pneumatic signals are typically used for control purposes to actuate the final control element in a control loop which is usually a control valve.
An “analogue” electronic signal is a voltage or current whose magnitude represents some physical measurement or control quantity.

The most popular form of signal transmission used in modern industrial instrumentation systems is the 4-20 mA DC standard. This is an analog signal standard, meaning that the electric current is used to proportionately represent measurements or control signals. Typically, a 4 mA current value represents 0% of scale, a 20 mA current value represents 100% of scale, and any current value in between 4 and 20 mA represents a commensurate percentage in between 0% and 100%.