The 4-20mA current loop is a very robust and popular sensor signalling standard. Current loops are ideal for data transmission because of their inherent insensitivity to electrical noise. In a 4-20mA current loop, all the signalling current flows through all devices. All the devices in the loop drop voltage due to the signal current flowing through them. The signalling current is not affected by these voltage drops as long as the power supply voltage is greater than the sum of the voltage drops around the loop at the maximum signal current of 20mA.
As shown in the diagram above, current supplied from the power supply flows through the loop wires with resistance, RW, to the transmitter and the 4 – 20mA transmitter regulates the current flow within the loop. The current allowed by the transmitter is called the loop current and it is proportional to the parameter that is being measured. The loop current flows back to the controller through the wire, and then flow through resistor, R, to ground and returns to the power supply. The current flowing through R produces a voltage that is easily measured by the analog input of a controller. For a 250 ohm resistor, the voltage will be 1VDC at 4mA and 5VDC at 20mA.